Conservatories

• Roof spaces adjacent to a room in a roof.

Xhese values, which are shown in Xables 5.3 and 5.4, can also be applied to similar situations in other buildings. For other unheated spaces it may be possible to calculate Rextra from:

where AINX is the total area of the elements separating the internal heated space from the unheated space, and AEXX is the total area of the elements separating the unheated space from the outside. However, if this formula yields a result for Rextra greater than 0.5 W/m2K, it should not be used.

Table 5.3 Extra thermal resistance due to unheated spaces - garages.

^extra

m2K/W

Garage type and description

Garage inside insulation layer of building

Garage outside insulation layer of building

Single, fully integral, sharing side wall, end wall and floor with building

0.68

0.33

Single, fully integral, sharing side wall and floor with building

0.54

0.25

Single, partially integral, projecting forward, sharing part of side wall, part of floor and end wall with building

0.56

0.26

Single, adjacent, sharing side wall only with building

0.23

0.09

Double, fully integral, sharing side wall, end wall and floor with building

0.59

0.28

Double, half integral, sharing side wall, half of end wall and half of floor with building

0.34

0.17

Double, partially integral, projecting forward, sharing part of side wall, part of floor and end wall with building

0.28

0.13

Double, adjacent, sharing side wall only with building

0.13

0.05

Adapted with permission from SAP 2001 [19]

Adapted with permission from SAP 2001 [19]

Table 5.4 Extra thermal resistance due to unheated spaces - various.

Type and description of unheated space

ReXtra m2K/W

Stairwell between heated space and external (exposed) wall

0.82

Stairwell between heated space and internal (not exposed) wall

0.90

Access corridor between heated space and external (exposed) wall, with another corridor above or below

0.31

Access corridor between heated space and external (exposed) wall, with another corridor above and below

0.28

Access corridor between heated space and internal (not exposed) wall, with another corridor above or below

0.43

Conservatory, double glazed, sharing one wall with heated space

0.06

Conservatory, double glazed, sharing two walls with heated space, i.e. in the angle between two walls

0.14

Conservatory, double glazed, sharing three walls with heated space, i.e. recessed

0.25

Conservatory, single glazed, sharing any number of walls with heated space

0.10

Loft space, between the roof covering and the wall of a heated room formed within a pitched roof above an insulated ceiling, for heat flow horizontally through the wall of the heated room

0.50

Loft space, between the roof covering and the wall of a heated room formed within a pitched roof above an insulated ceiling, for heat flow vertically from/through the ceiling of the room below

0.50

Adapted with permission from SAP 2001 [19]